Parallel Processing UPS SANUPS E23A/E33A E23A503 in Shanghai, China

Specifications

Condition
new
Ups topology
Parallel processing
No. of input phases/wires
3-phase 3-wire
Rated input voltage[v]
200/205/210
Rated input frequency[hz]
50/60
Input power factor
0.98 or greater
Required input capacity[kva]
50 or less
No. of output phases/wires
3-phase 3-wire
Rated output capacity[kva]
50
Rated output capacity[kw]
40
Rated output voltage[v]
200/205/210
Output voltage regulation
During grid operation: Within -8% to +10% of rated voltage (This is the factory setting, and can be changed with settings.) During battery operation: Within ±2% of rated voltage
Rated output frequency[hz]
50/60
Output frequency regulation
During grid operation: Within ±4% of rated frequency (This is the factory setting, and can be changed with settings.) During battery operation: Within ±0.1% of rated frequency
Output transient voltage fluctuation
For 0⇔100% load step changes: Within ±5% of rated voltage (during battery operation) Settling time: Within 50 ms
Output overload capability
During grid operation: 200% (for 30 s), 800% (for 0.5 s) During battery operation: 125% (for 10 min), 150% (for 1 min)
Output transfer time
No interruption
Energy storage device type
Small-sized valve-regulated lead-acid (VRLA) battery
Standard backup time[min]
10
Operating temperature range
0 ~ +40℃
Operating humidity range
30 to 90% (non-condensing)
Acoustic noise[db]
65
Heat dissipation[w]
2600
Mass[kg]
1550
Subcategory
Sanups e23a/e33a
Listing ID
75800582

Description

Contact the seller for more information about this listings.

Contact Seller for Price

Manufacturer
N/A
Model
E23A503
Location
🇨🇳 Shanghai, China

Interested in this machine?

This seller has been contacted 1 time in the last week.

Seller Responsiveness:

5.0
Get Financing

Our financing partner can help you get fast, easy, and affordable financing for your equipment purchase